| 2001-01-08 00:00:00 | 1)TOILET ROOM INSIDE THE RESTROOM IS |
| | A COMPONENT OF THE RESTROOM AND THE |
| | WIDTH OF THE TOILET ROOM SHALL BE MIN. |
| | 83"(IF LAV.IS LOCATED ADJACENT TO W.C.) |
| | SEE FACBC SEC.4.17.3. |
| | |
| | 2)SHOW REQUIRED WHEELCHAIR TURNING SPACE |
| | IN RESTROOMS 203,205,219,216.PER FACBC |
| | SEC.4.2.3. |
| | |
| | 3)WAINSCOTING TO 4' IS REQD.IN ALL THE |
| | TOILET ROOMS PER SBC SEC.1204.2. |
| | |
| | 4)DISHWASHER SHALL DISCHARGE TO SANITARY |
| | PER CITY ORDINANCE. |
| | |
| | 5)DOORS CANNOT SWING INTO CLEAR FLOOR |
| | SPACE OF FIXTURES.FACBC SEC.4.17.5,4.22. |
| | |
| | 6)SUBMIT COMPLETE GAS DRAWING FOR RE- |
| | VIEW.COMPLY W/ATTACHED REQS. |
| | |
| | 7)SANITARY SYSTEM REQUIRES ONE MAIN |
| | VENT THRU ROOF FOR USE WITH AUTOMATIC |
| | AIR ADMITTANCE VALVES PER MANUF. |
| | INSTALLATION INSTRUCTIONS. |
| | |
| | 8)CONDENSATE DISPOSAL SHALL COMPLY W/ |
| | SMC SEC.304.8.3. |
| | |
| | 9)RECEPTORS RECEIVING INDIRECT WASTES |
| | SHALL BE FLOOR SINKS PER SPC SEC.807.1. |
| | |
| | 10)DESIGN OF DRAIN SYSTEM FOR FLOOR |
| | SINKS/FLOOR DRAINS SHALL COMPLY W/SPC |
| | SEC.921. |
| | |
| | 11)SHT.P-9-DRINKING FOUNTAINS ARE NOT |
| | SHOWN ON SANITARY RISER. |
| | |
| | 12)WATER HEATER IN JANITOR CLOSET SHALL |
| | BE READILY ACCESSIBLE PER SPC 501.7. |
| | |
| | CALL 561-659-8096,EXT.8377 IF YOU HAVE |
| | ANY QUESTIONS. |
| | TIMOTHY LARGE |
| | PLUMBING PLANS EXAMINER. |