Plan Review Notes
Plan Review Notes For Permit 00061369
Permit Number 00061369
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001)TOILET ROOM INSIDE THE RESTROOM IS
 A COMPONENT OF THE RESTROOM AND THE
 WIDTH OF THE TOILET ROOM SHALL BE MIN.
 83"(IF LAV.IS LOCATED ADJACENT TO W.C.)
 SEE FACBC SEC.4.17.3.
  
 2)SHOW REQUIRED WHEELCHAIR TURNING SPACE
 IN RESTROOMS 203,205,219,216.PER FACBC
 SEC.4.2.3.
  
 3)WAINSCOTING TO 4' IS REQD.IN ALL THE
 TOILET ROOMS PER SBC SEC.1204.2.
  
 4)DISHWASHER SHALL DISCHARGE TO SANITARY
 PER CITY ORDINANCE.
  
 5)DOORS CANNOT SWING INTO CLEAR FLOOR
 SPACE OF FIXTURES.FACBC SEC.4.17.5,4.22.
  
 6)SUBMIT COMPLETE GAS DRAWING FOR RE-
 VIEW.COMPLY W/ATTACHED REQS.
  
 7)SANITARY SYSTEM REQUIRES ONE MAIN
 VENT THRU ROOF FOR USE WITH AUTOMATIC
 AIR ADMITTANCE VALVES PER MANUF.
 INSTALLATION INSTRUCTIONS.
  
 8)CONDENSATE DISPOSAL SHALL COMPLY W/
 SMC SEC.304.8.3.
  
 9)RECEPTORS RECEIVING INDIRECT WASTES
 SHALL BE FLOOR SINKS PER SPC SEC.807.1.
  
 10)DESIGN OF DRAIN SYSTEM FOR FLOOR
 SINKS/FLOOR DRAINS SHALL COMPLY W/SPC
 SEC.921.
  
 11)SHT.P-9-DRINKING FOUNTAINS ARE NOT
 SHOWN ON SANITARY RISER.
  
 12)WATER HEATER IN JANITOR CLOSET SHALL
 BE READILY ACCESSIBLE PER SPC 501.7.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.