Plan Review Notes
Plan Review Notes For Permit 00061369
Permit Number 00061369
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001) TRAVEL DISTANCE NOTE ON PLANS IS
 STILL INCORRECT. TRAVEL DISTANCE NOTE
 SHOULD READ 200 FEET INSTEAD OF 250
 FEET.
 2) NEW WOOD GUARDRAIL TO COMPLY WITH
 NFPA 101, LIFE SAFETY CODE REQUIREMENTS,
 1985 EDITION.
 3) TWO STEPS SHOWN ON PAGE A4.2 IS NOT
 PROPER. A MINIMUM OF THREE STEPS SHALL
 BE PROVIDED AT 7" EACH OR A RAMP IS
 REQUIRED.
 4) WATER CURTAIN WITH FIRE SPRINKLER
 HEADS NO FARTHER THAN 6 FEET APART ARE
 REQUIRED AT NORTHEAST STAIR.