| Plan Review Notes For Permit 00061369 |
| Permit Number |
00061369 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) TRAVEL DISTANCE NOTE ON PLANS IS | | | STILL INCORRECT. TRAVEL DISTANCE NOTE | | | SHOULD READ 200 FEET INSTEAD OF 250 | | | FEET. | | | 2) NEW WOOD GUARDRAIL TO COMPLY WITH | | | NFPA 101, LIFE SAFETY CODE REQUIREMENTS, | | | 1985 EDITION. | | | 3) TWO STEPS SHOWN ON PAGE A4.2 IS NOT | | | PROPER. A MINIMUM OF THREE STEPS SHALL | | | BE PROVIDED AT 7" EACH OR A RAMP IS | | | REQUIRED. | | | 4) WATER CURTAIN WITH FIRE SPRINKLER | | | HEADS NO FARTHER THAN 6 FEET APART ARE | | | REQUIRED AT NORTHEAST STAIR. |
|