| Plan Review Notes For Permit 00061369 |
| Permit Number |
00061369 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW | | | (1) SHT P-A2.3 REST RM #202,206 DOORS TO | | | SWING OUT. FACBC 4.23.2 | | | (2) SHT P-4 JANITORS CLOSET WTR. HTR TO | | | BE READLY ACCESSIBLE SPS 94 SEC 501.7 | | | (3) SHT P-4 KITCHEN #223 CONTACT | | | DEPT OF HOTEL BUSINESS REGULATION FOR | | | THEIR PLAN REVIEW 954-958-5520. | | | (4) SHT P-7 DISHWASHER TO SANITARY SEWER | | | LOCAL ORDINANCE REGIONAL SEWER PLANT. | | | (5) SHT P-7 GAS PIPING ISOMETRIC REQ. | | | SHOW TOTAL DEVELOPED LGTH,TOTAL BTU'S | | | BTU'S OF EA APPLIANCE,TYPE OF MATERIAL, | | | PSI ON SYSTEM.SGC 94 SEC 104.2 | | | (6) SHT P-8,9 AIR ADMITANCE VALVES, | | | ONE VTR ON EACH SANITARY & GREASE WASTE | | | LATERIAL TO BUILDING SEWER. | | | END OF COMMENTS |
|