2001-01-08 00:00:00PLUMBING PLAN REVIEW
 (1) SHT P-A2.3 REST RM #202,206 DOORS TO
 SWING OUT. FACBC 4.23.2
 (2) SHT P-4 JANITORS CLOSET WTR. HTR TO
 BE READLY ACCESSIBLE SPS 94 SEC 501.7
 (3) SHT P-4 KITCHEN #223 CONTACT
 DEPT OF HOTEL BUSINESS REGULATION FOR
 THEIR PLAN REVIEW 954-958-5520.
 (4) SHT P-7 DISHWASHER TO SANITARY SEWER
 LOCAL ORDINANCE REGIONAL SEWER PLANT.
 (5) SHT P-7 GAS PIPING ISOMETRIC REQ.
 SHOW TOTAL DEVELOPED LGTH,TOTAL BTU'S
 BTU'S OF EA APPLIANCE,TYPE OF MATERIAL,
 PSI ON SYSTEM.SGC 94 SEC 104.2
 (6) SHT P-8,9 AIR ADMITANCE VALVES,
 ONE VTR ON EACH SANITARY & GREASE WASTE
 LATERIAL TO BUILDING SEWER.
 END OF COMMENTS