Plan Review Notes
Plan Review Notes For Permit 00061369
Permit Number 00061369
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DENIED: ********************************
  
 1. PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2
 2. ENERGY EFFIECIENCY RATING 0F AHU TO
 BE PROVIDED
 3. PROVIDE IN THE JANITOR'S CLOSET AN
 EXHAUST FAN PER 1997 SMC 503.2
 4. DUCT MATERIAL SCHEDULE REQUIRED
  
 NOTES: SEPERATE PERMIT FOR HOODS, GAS,
 FIER-SUPPRESSION SYSTEM, WALK-IN
 COOLERS/FREEZERS.