| Plan Review Notes For Permit 00061369 |
| Permit Number |
00061369 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) TRAVEL DISTANCES TO EXITS IN NEW | | | ASSEMBLY OCCUPANCIES SHALL NOT EXCEED | | | 200 FEET. | | | 2) ALL EXIT DOORS SUBJECT TO AN | | | OCCUPANCY LOAD OF 100 OR MORE PERSONS | | | ARE TO BE EQUIPPED WITH APPROVED PANIC | | | HARDWARE. IF THESE DOORS ARE FIRE RATED | | | THEN THEY ARE TO BE EQUIPPED WITH | | | APPROVED FIRE EXIT PANIC HARDWARE. | | | 3) EXHIBITION HALL TO PROVIDE PROVISIONS | | | FOR AT LEAST TWO HANDICAPPED PERSONS. | | | 4) INTERIOR FINISH SHALL BE CLASS A OR | | | B. | | | 5) NO SEATING ARRANGEMENT SHOWN ON | | | DRAWINGS. | | | 6) ALL STORAGE ROOMS SHALL BE SEPARATED | | | FROM OTHER PARTS OF THE BUILDING BY | | | AT LEAST ONE HOUR AND FIRE SPRINKLERS. | | | 7) STANDPIPE LOCATIONS NOT SHOWN FOR | | | EXHIBITION HALL. | | | 8) NORTH ENTRY STAIR TO BE SLIP | | | RESISTANT. | | | 9) |
|