2001-01-08 00:00:001) TRAVEL DISTANCES TO EXITS IN NEW
 ASSEMBLY OCCUPANCIES SHALL NOT EXCEED
 200 FEET.
 2) ALL EXIT DOORS SUBJECT TO AN
 OCCUPANCY LOAD OF 100 OR MORE PERSONS
 ARE TO BE EQUIPPED WITH APPROVED PANIC
 HARDWARE. IF THESE DOORS ARE FIRE RATED
 THEN THEY ARE TO BE EQUIPPED WITH
 APPROVED FIRE EXIT PANIC HARDWARE.
 3) EXHIBITION HALL TO PROVIDE PROVISIONS
 FOR AT LEAST TWO HANDICAPPED PERSONS.
 4) INTERIOR FINISH SHALL BE CLASS A OR
 B.
 5) NO SEATING ARRANGEMENT SHOWN ON
 DRAWINGS.
 6) ALL STORAGE ROOMS SHALL BE SEPARATED
 FROM OTHER PARTS OF THE BUILDING BY
 AT LEAST ONE HOUR AND FIRE SPRINKLERS.
 7) STANDPIPE LOCATIONS NOT SHOWN FOR
 EXHIBITION HALL.
 8) NORTH ENTRY STAIR TO BE SLIP
 RESISTANT.
 9)