2001-01-08 00:00:00DENIED:*********************************
 INDICATE THE RETURN AIR FROM MAIN STORE
 AREA TO THE AHU.
 PROVIDE CFM VALUE OF EACH DROP IN MAIN
 STORE AREA.
 PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2.
 REQUIRED OUTSIDE AIR PER ASHRAE 62-89.
 PROVISO: DUCT MATERIAL & CONNECTION
 DETAILS REQUIRED PER FLORIDA
 ENERGY EFFICIENCY CODE.