| Plan Review Notes For Permit 00061347 |
| Permit Number |
00061347 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED:********************************* | | | INDICATE THE RETURN AIR FROM MAIN STORE | | | AREA TO THE AHU. | | | PROVIDE CFM VALUE OF EACH DROP IN MAIN | | | STORE AREA. | | | PROVIDE AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2. | | | REQUIRED OUTSIDE AIR PER ASHRAE 62-89. | | | PROVISO: DUCT MATERIAL & CONNECTION | | | DETAILS REQUIRED PER FLORIDA | | | ENERGY EFFICIENCY CODE. |
|