| Plan Review Notes For Permit 00061244 |
| Permit Number |
00061244 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | `1)WIDTH OF HANDICAP TOILET STALL DOOR | | | OPENING SHALL COMPLY W/FACBC SEC.4.17.5 | | | AND FIGURE 30.SHT.A1. | | | | | | 2)MIN.WIDTH OF HANDICAP STALL SHALL BE | | | 83" PER FACBC SEC.4.17.3,SPC 403.1 | | | | | | 3)THE WATER HEATER LISTING IS OVER | | | 200,000 BTU'S AND THEREFORE CLASSIFIED | | | AS A BOILER AND SHALL COMPLY W/THE | | | FOLLOWING CODE SECS.: | | | A)SGC SECS.507.7,507.8 | | | B)SMC SEC.1003.1-1003.4. | | | C)SMC SEC.1004.1,1004.2. | | | D)TABLE 1003,FOOTNOTE #8. | | | E)SBC 704.1.3.3. | | | SUBMIT MANUF.SHEETS FOR BOILER. | | | | | | 4)SHT.A4.1-DRY VENTS NOT PERMITTED PER | | | SPC SEC.906.2.1.(SEE FLOOR SINK & W.C.) | | | | | | 5)WATER CLOSETS AND FIXTURE BRANCHES NOT | | | PERMITTED ON WET VENTS PER COUNTYWIDE | | | AMENDMENTS TO SPC SEC.911.1.1. | | | | | | 6)CIRCUIT AND LOOP SYSTEM SAHLL COMPLY | | | W/SPC SEC.914.2. | | | | | | 7)SIZE OF HORIZONTAL DRAIN FOR W.C.'S IN | | | WOMEN'S R.R.SHALL COMPLY W/SPC TABLE | | | 714.2,FOOTNOTE #2. | | | | | | 8)FLOOR SINK AND HAND SINK SHALL | | | DISCHARGE TO G.W.PER 1004.1,1004.4. | | | | | | 9)SHT.A4.1-SIZING/DESIGN OF GAS SYSTEM | | | SHALL COMPLY W/SGC.SYSTEM IS UNDERSIZED | | | AS DESIGNED.SEE ATTACHED LIST FOR GAS | | | DRAWING REQS. | | | | | | CALL 561-659-8096 EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE,PLUMBING PLANS EXAMINER. |
|