| 2001-01-08 00:00:00 | SIZE OF HANDICAP STALL SHALL COMPLY W/ |
| | FACBC SEC.4.17.3 |
| | |
| | DISHWASHER SHALL DISCHARGE TO SANITARY |
| | PER CITY OF WPB ORDINANCE. |
| | |
| | DRY VENTS NOT PERMITTED PER SPC SEC. |
| | 906.2.1.(SEE RESTROOMS AND GREASY WASTE) |
| | |
| | WATER CLOSETS AND FIXTURE BRANCHES NOT |
| | PERMITTED ON WET VENTS PER COUNTYWIDE |
| | AMENDMENTS SEC.911.1.1. |
| | |
| | CIRCUIT AND LOOP SYSTEM SHALL COMPLY W/ |
| | SPC SEC.914.2. |
| | |
| | SIZE OF HORIZ.DRAIN FOR WATER CLOSETS |
| | AND URINALS SHALL COMPLY W/SPC TABLE |
| | 714.2,FOOTNOTE #2. |
| | |
| | FLOOR SINK AND HAND SINK SHALL DRAIN TO |
| | GREASY WASTE PER SPC SEC.1004.4. |
| | |
| | TWO WAY CLEANOUT REQD.ON BUILDING DRAIN |
| | (GREASY WASTE)PER SPC SEC.710.4. |
| | |
| | FLOOR SINK SHALL BE USED IN LIEU OF HUB |
| | DRAIN.SPC 807.1.2.,807.1.3. |
| | |
| | A UNION IS REQD.DOWNSTREAM OF GAS |
| | CONTROLS PER NFPA 54 SEC.5.5.4. |
| | |
| | SUBMIT COPY OF/OR MAKE REFERENCE TO |
| | APPLICABLE GAS SIZING TABLE USED FOR |
| | SYSTEM DESIGN.SYSTEM DOES NOT COMPLY W/ |
| | SGC FOR PROPER SIZING. |
| | |
| | HEATERS OVER 200,000 BTU'S SHALL COMPLY |
| | W/SPC SEC.507.7. |
| | |
| | SIZE THE C.W.DROP TO THE MENS/LADIES |
| | RESTROOMS.COMPLY W/COUNTYWIDE AMENDMENTS |
| | SEC.607.7. |
| | |
| | WATER SUPPLY TO RESTROOMS AND KIT.AREA |
| | SHALL COMPLY W/SPC SEC.610.4.1.,610.4.2. |
| | |
| | WATER DIAGRAM SHOWS OVER 2 FIXTURES ON |
| | 1/2" C.W.LINE.COMPLY W/SPC SEC.607.7. |
| | |
| | GREASY WASTE SYSTEM SHOWS 6"LINE |
| | DRAINING INTO 4"LINE.COMPLY W/SPC SEC. |
| | 307.5. |
| | |