Plan Review Notes
Plan Review Notes For Permit 00061244
Permit Number 00061244
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SIZE OF HANDICAP STALL SHALL COMPLY W/
 FACBC SEC.4.17.3
  
 DISHWASHER SHALL DISCHARGE TO SANITARY
 PER CITY OF WPB ORDINANCE.
  
 DRY VENTS NOT PERMITTED PER SPC SEC.
 906.2.1.(SEE RESTROOMS AND GREASY WASTE)
  
 WATER CLOSETS AND FIXTURE BRANCHES NOT
 PERMITTED ON WET VENTS PER COUNTYWIDE
 AMENDMENTS SEC.911.1.1.
  
 CIRCUIT AND LOOP SYSTEM SHALL COMPLY W/
 SPC SEC.914.2.
  
 SIZE OF HORIZ.DRAIN FOR WATER CLOSETS
 AND URINALS SHALL COMPLY W/SPC TABLE
 714.2,FOOTNOTE #2.
  
 FLOOR SINK AND HAND SINK SHALL DRAIN TO
 GREASY WASTE PER SPC SEC.1004.4.
  
 TWO WAY CLEANOUT REQD.ON BUILDING DRAIN
 (GREASY WASTE)PER SPC SEC.710.4.
  
 FLOOR SINK SHALL BE USED IN LIEU OF HUB
 DRAIN.SPC 807.1.2.,807.1.3.
  
 A UNION IS REQD.DOWNSTREAM OF GAS
 CONTROLS PER NFPA 54 SEC.5.5.4.
  
 SUBMIT COPY OF/OR MAKE REFERENCE TO
 APPLICABLE GAS SIZING TABLE USED FOR
 SYSTEM DESIGN.SYSTEM DOES NOT COMPLY W/
 SGC FOR PROPER SIZING.
  
 HEATERS OVER 200,000 BTU'S SHALL COMPLY
 W/SPC SEC.507.7.
  
 SIZE THE C.W.DROP TO THE MENS/LADIES
 RESTROOMS.COMPLY W/COUNTYWIDE AMENDMENTS
 SEC.607.7.
  
 WATER SUPPLY TO RESTROOMS AND KIT.AREA
 SHALL COMPLY W/SPC SEC.610.4.1.,610.4.2.
  
 WATER DIAGRAM SHOWS OVER 2 FIXTURES ON
 1/2" C.W.LINE.COMPLY W/SPC SEC.607.7.
  
 GREASY WASTE SYSTEM SHOWS 6"LINE
 DRAINING INTO 4"LINE.COMPLY W/SPC SEC.
 307.5.
  
 IF YOU HAVE ANY QUESTIONS I CAN BE
 REACHED AT 561-659-8096,EXT.8377.
 TIMOTHY LARGE,PLUMBING PLANS EXAMINER.