2001-01-08 00:00:00DENIED:******************************
 THE FOLLOWING REQUIREMENTS ARE TO BE
 PROVIDED:
 1. PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2.
 2. DUCT MATERIAL SCHEDULE PER FLORIDA
 ENERGY CODE.
 3. FLEX DUCT CONNECTION DETAIL.
 4. GRILLE, DIFFUSERS AND REGISTERS
 SCHEDULE.
  
 PROVISO:
 SEPERATE PERMIT REQUIRED FOR HOOD,
 GAS, FIRE-SUPPRESSION SYSTEM,WALK-IN
 COOLERS/FREEZERS.
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION BY FIRE ALARM SYS-
 TEM OR TIED-IN TO HORN AND STROBE AS
 PER NFPA 90A 4.4.4.2 AND 4.4.4.3..