| 2001-01-08 00:00:00 | **************** PROVISO ************* | | | | | | 1)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125%. PLEASE SHOW LOAD CALCULATIONS. | | | | | | | | | 2)NOTE: PLEASE SUBMIT ALL AIC RATINGS | | | OF ALL EQUIPMENT. MAINS/PANELS ARE TO BE | | | RATED FOR ALL AVAILABLE FAULT CURRENTS. | | | 110-9/215-5 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|