| Plan Review Notes For Permit 00061141 |
| Permit Number |
00061141 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-01-31 00:00:00 | *********** REVISION NEEDED | | | ************1) NOTE: PLEASE NOTE THAT A | | | MAIN DSCONNECT HAS BEEN ADDED TO PLANS | | | ON SHEET E-5 FOR PANEL "K". NO SPECS | | | WERE SUBMITTED | | | FOR THIS EQUIPMENT. PLEASE DO SO. | | | NOW THAT THERE IS A MAIN INLINE FROM | | | TRANSFORMER, DOES PANEL "K " STILL HAVE | | | A ,MAIN? | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRNET PER 110-9. | | | THIS IS REQ`D FOR NEW PANEL "K " DISC. | | | | | | 3)NOTE: PLANS HAVE BEEN REDRAWN BY HAND | | | AND NEEDS TO BE RE-DONE UNDER | | | ADMINISTRATIVE CODE BEING SUBMITTED FOR | | | RECORD. | | | SEE SECTION 104.2.1 AND 104.2.7 FOR | | | QUALITY OF PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. PLANS ARE FOR A"T.C.O" | | | AND | | | MUST BE DONE BEFORE"C.O.". | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|