| Date |
Text |
| 2001-01-08 00:00:00 | HANDICAP STALLS ARE REQUIRED IN THE |
| | MALE AND FEMALE TOILET ROOMS PER FACBC |
| | SEC.4.1.2.(6),4.17.3,4.22.4. |
| | |
| | LAVATORIES ARE REQD.IN THE HANDICAP |
| | STALLS PER FACBC SEC.4.17.3.AND SIZE |
| | SHALL COMPLY W/FACBC SEC.4.17.3. |
| | |
| | SHOW THE REQUIRED WHEELCHAIR TURNING |
| | SPACE IN THE TOILET ROOMS PER FACBC SEC. |
| | 4.2.3. |
| | |
| | HEIGHT OF URINAL SHALL COMPLY W/FACBC |
| | SEC.4.18.2. |
| | |
| | SHT.P-1-FLOOR DRAINS AND FLOOR SINKS |
| | ARE NOT PROPERLY VENTED PER SPC SEC. |
| | 901.2,TABLE 908.1. |
| | |
| | SHT.P-3-VENT SIZING SHALL COMPLY W/SPC |
| | TABLE 920.2.(DETERMINE BY FIXTURE UNIT |
| | LOAD.) |
| | |
| | DISHWASHER SHALL DISCHARGE TO THE |
| | SANITARY SYSTEM PER CITY OF WPB |
| | ORDINANCE. |
| | |
| | A UNION IS REQD.ON THE GAS CONTROLS PER |
| | NFPA 54 SEC.5.5.4. |
| | |
| | SUBMIT COPY OF/OR MAKE REFERENCE TO THE |
| | APPROPRIATE GAS SIZING TABLE USED TO |
| | DESIGN THE GAS SYSTEM.COMPLY W/ SGC SEC. |
| | 305.4. |
| | |
| | INDICATE TYPE OF PIPING MATERIAL USED |
| | FOR THE GAS SYSTEM.COMPLY W/SGC SEC.306. |
| | |
| | RECALCULATE THE BTU LOAD.MY CALCULATIONS |
| | ARE 201,198.PLEASE VERIFY.SGC 305.3. |
| | |
| | SUBMIT LEGEND FOR ALL FIXTURES NOTED BY |
| | NUMBERS ON SHT.P-4.COUNTYWIDE AMENDMENTS |
| | TO SPC SEC.104.2.1. |
| | |
| | OVER 2 FIXTURES SUPPLIED BY 1/2"C.W.& |
| | OVER 4 FIXTURES SUPPLIED BY 1/2" H.W. |
| | PER COUNTYWIDE AMENDMENTS TO SPC SEC. |
| | 607.7 |
| | |
| | SHT.P-5-NOTE #14-PIPING INSULATION SHALL |
| | COMPLY W/F.E.C. TABLE 4-11. |
| | |
| | SUBMIT MANUF.SHEETS FOR GAS EQUIPMENT. |
| | EQUIPMENT SHALL BE APPROVED PER SGC SEC. |
| | 402.1.,501.2. |
| | |
| | GARBAGE DISPOSAL SHALL DISCHARGE TO THE |
| | SANITARY PER 1004.11. |
| | |
| | SUBMIT ADDITIONAL INFORMATION FOR THE |
| | WATER HEATER FLUE.INSTALLATION SHALL |
| | COMPLY W/STANDARD GAS AND STANDARD |
| | MECHANICAL CODES.(1997 EDITION.) |