| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SUBMIT RATING AND ELEC-R | | | -TRICAL DETAIL ON DIMMER PANEL. | | | | | | 2)NOTE:PLEASE NOTE THAT GROUNDING | | | ATTACHMENT NEEDS TO GO TO BLDG. STEEL | | | ALSO, BOND AS REQ`D BY 250 OF NEC. | | | | | | 3)NOTE: PLEASE SHOW LOAD CALCUALTIONS. | | | PLEASE SHOW ALL CONTINUOUS LOADS AT 125% | | | INCLUDING LIGHTING ETC. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 ETX 8372 |
|