| Plan Review Notes For Permit 00061141 |
| Permit Number |
00061141 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1. FLORIDA ENERGY SHEETS SIGNED AND | | | SEALED BY DESIGNER OF RECORD AND OWNER. | | | 2. INDICATE FIRE SEPERATION BETWEEN | | | OCCUPANCIES 2 HR REQUIRED. SHOW LOCATION | | | HORZONTIAL AND VERTICAL INDICATE UL | | | RATING FOR ALL ASSEMBLIES. | | | 3. EXTERIOR GLAZING IMPACT RESISTANT, | | | PROVIDE PRODUCT APPROVAL. | | | IF SHUTTERS USED, PROVIDE WIND LOAD | | | INFORMATION FOR ALL EXTERIOR GLAZING | | | PROVIDE PRODUCT APPROVAL FOR SHUTTERS. | | | PROVIDE PLAN FOR INSTULLATION SIGNED BY | | | OWNER SHOW STORAGE LOCATION IN UNIT. | | | SHUTTER PLANS ARE SUBJECT TO APPROVAL | | | BY THE BUILDING OFFICIAL SEE CITY POLICY | | | 4. FIRE SPRINKLER CONTRACTOR TO APPLY | | | FOR PERMIT. | | | 5. EXITS, SECOND MEANS OF EGRESS DEFINED | | | ON PLANS IS BLOCKED BY A TABLE. REVISE. | | | 6. SIGNS REQUIRE SEPERATE PERMITS. |
|