| Plan Review Notes For Permit 00061076 |
| Permit Number |
00061076 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED******************************* | | | 1. PROVIDE OUTSIDE CALCULATIONS PER | | | ASHRAE 62-89. | | | 2. REQUIRES AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2. | | | 3. NFPA 90A REQUIRES NOTICATION OF | | | ACTIVATION OF DUCT SMOKE DETECTOR BY | | | VISUAL AND AUDIBLE SIGNAL. THIS IS | | | NOT REQUIRED TO BE TIED IN TO THE | | | MALL FIRE ALARM SYSTEM. |
|