| Plan Review Notes For Permit 00061076 |
| Permit Number |
00061076 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ******************* UNSAT ************** | | | | | | 1)NOTE: PLEASE SHOW ALL DIMMER/SWITCH | | | LOCATIONS. | | | | | | 2)NOTE: PLEASE NOTE THAT EXIT LIGHTS ARE | | | SHOWN ON SWITCH #6??? THIS IS NOT | | | PERMITTED AND EMERGENCY LIGHTS ALSO. | | | | | | 3)NOTE:PLEASE NOTE THAT LOAD OF TRACK | | | LIGHTING NEEDS TO BE SHOWN SEPARATE | | | IN CALCULATIONS.ALSO AT 125% FOR CONTIN- | | | UOUS LOAD.22-12 | | | | | | 4)NOTE:SHOW WINDOW IS SHOWNON PANEL AT | | | .4 KW AND ON LOAD CALCS AT .45KW? | | | PLEASE CORRELATE | | | | | | 5)NOTE:PLEASE SUBMIT AIC RATING OF MAIN | | | DISCONNECTS.MAINS//PANLES ARE TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT | | | PER 110-9/215-5 | | | | | | ^0NOTE:LIGHTING IS SHOWN ON LOAD CALCS | | | AT 1,630,,,3W-PER-SQ-AT 125% YOU SHOW | | | TOTAL AT 4,890? PLEASE SHOW,,,I COME UP | | | WITHA DIFFERENT TOTAL. | | | | | | 7)NOTE:PLEASE SEE LOAD CALCS,,YOU SHOW | | | LOADS FOR WATER HEATERS AT 3500 EACH | | | AND DIFFERENT TOTAL LOAD?? THIS ALSO | | | DOES NOT CORRELATE WITH PANEL SCHEDLUE? | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 561-659-8096 EXT 8372 | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW |
|