| Plan Review Notes For Permit 00061071 |
| Permit Number |
00061071 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED**************************** | | | PROVIDE THE FOLLOWING ITEM: | | | | | | 1. OUTSIDE AIR CALCULATIONS PER ASHRAE | | | 62-89. | | | 2. AIR BALANCE SCHEDULE TO SHOW COMPLI- | | | -ANCE WITH 1997 SMC 501.2. | | | | | | 3. NFPA 90A REQUIRES NOTIFICATION OF | | | ACTIVATION OF DUCT SMOKE DETECTOR BY | | | VISUAL AND AUDIBLE SIGNAL. THIS IS | | | NOT REQUIRED TO BE TIED TO THE MALL | | | FIRE ALARM SYSTEM. |
|