Plan Review Notes
Plan Review Notes For Permit 00061071
Permit Number 00061071
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DENIED****************************
 PROVIDE THE FOLLOWING ITEM:
  
 1. OUTSIDE AIR CALCULATIONS PER ASHRAE
 62-89.
 2. AIR BALANCE SCHEDULE TO SHOW COMPLI-
 -ANCE WITH 1997 SMC 501.2.
  
 3. NFPA 90A REQUIRES NOTIFICATION OF
 ACTIVATION OF DUCT SMOKE DETECTOR BY
 VISUAL AND AUDIBLE SIGNAL. THIS IS
 NOT REQUIRED TO BE TIED TO THE MALL
 FIRE ALARM SYSTEM.