| Plan Review Notes For Permit 00061071 |
| Permit Number |
00061071 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE: EXIT LIGHTS AND EMERGENCY LIGHTS | | | ARE SHOWN AS BEING SWITCHED? THIS IS NOT | | | PERMITTED. | | | | | | 2)NOTE: PLEASE SUBMIT THE AIC RATING FOR | | | ALL EQUIPMENT MAINS/PANELS BEING INSTALL | | | -ED. MUST BE RATED FOR THE AVIALABLE | | | FAULT CURRENT. PER 110-9 | | | | | | 3)NOTE: PLEASE SHOW THE LOADS FIGURED | | | FOR TRACK LIGHTING PER 220-12-B | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 561-659-8096 EXT 8372 | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW |
|