| Plan Review Notes For Permit 00061043 |
| Permit Number |
00061043 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************** PROVISO ************** | | | | | | 1)NOTE: SMOKE DETECTOR IS REQ`D ON | | | EACH LEVEL AND OUTSDIE BEDROOM. | | | 1996 NFPA-72 2-2.1.1.1 | | | | | | 2)NOTE:PLEASE LIST ON PANEL SCHEDULE | | | THE REQ`D DEDICATED BATH(S) AS PER | | | 210-11-C-3 | | | | | | 3)NOTE:PLEASE LABEL ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECTE | | | AS PER 210-8-A-6 | | | | | | 4)NOTE:PLEASE SHOW THE REQ`D WP GFI | | | OUTLET FOR NEW A/C CU. | | | | | | 5)NOTE:PLEASE SUBMIT THE AIC RATING OF | | | NEW 200 AMP PANEL. PANELS/MAINS ARE TO | | | BE RATED FOR THE AVAILABLE FAULT CURRENT | | | AS PER 110-9/215-5 | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW BEFORE ANY ROUGH ELECTRICAL | | | INSPECTION IS CALLED IN. IF THERE ANY | | | QUESTIONS PLEASE CALL D.PALMER AT | | | 659-8096 EXT 8372 |
|