Plan Review Notes
Plan Review Notes For Permit 00061043
Permit Number 00061043
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************** PROVISO **************
  
 1)NOTE: SMOKE DETECTOR IS REQ`D ON
 EACH LEVEL AND OUTSDIE BEDROOM.
 1996 NFPA-72 2-2.1.1.1
  
 2)NOTE:PLEASE LIST ON PANEL SCHEDULE
 THE REQ`D DEDICATED BATH(S) AS PER
 210-11-C-3
  
 3)NOTE:PLEASE LABEL ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECTE
 AS PER 210-8-A-6
  
 4)NOTE:PLEASE SHOW THE REQ`D WP GFI
 OUTLET FOR NEW A/C CU.
  
 5)NOTE:PLEASE SUBMIT THE AIC RATING OF
 NEW 200 AMP PANEL. PANELS/MAINS ARE TO
 BE RATED FOR THE AVAILABLE FAULT CURRENT
 AS PER 110-9/215-5
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ANY
 QUESTIONS PLEASE CALL D.PALMER AT
 659-8096 EXT 8372