| Plan Review Notes For Permit 00061010 |
| Permit Number |
00061010 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) NO INTERIOR FINISH INFORMATION | | | PROVIDED WITH PLANS. PLEASE PROVIDE | | | INTERIOR FINISH INFORMATION FOR | | | WALLS AND CEILINGS. | | | 2) NO SEATING DIAGRAM PROVIDED FOR | | | DINING ROOM AND MEETING ROOM. PLEASE | | | PROVIDE SEATING DIAGRAM FOR DINING ROOM | | | AND MEETING ROOM. | | | 3) IS THERE ANY FIRE SEPARATION FOR | | | THE STORAGE ROOMS. | | | 4) OCCUPANT LOAD TO BE DETERMINED BY | | | THIS OFFICE. | | | 5) AN ADDITIONAL EMERGENCY LIGHT | | | FIXTURE IS REQUIRED IN THE REAR OF | | | UNIT 417. |
|