| Plan Review Notes For Permit 00060867 |
| Permit Number |
00060867 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** PROVISO ************** | | | | | | 1)NOTE: NEED TO SHOW ALL BRANCH CIRCUIT | | | #`S ON PLANS. PLEASE SUBMIT EXISTING | | | PANEL SIZE AND PROVIDE REVISED PANEL | | | SCHEDULE TO CORRELATE TOPLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW BEFORE ANY ROUGH ELECTIRCAL | | | INSPECTION IS CALLED IN. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL 659-8096 EXT | | | 8372 |
|