| Plan Review Notes For Permit 00060865 |
| Permit Number |
00060865 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED | | | | | | 1)PROVIDE 2 CURRENT COPIES OF METRO-DADE | | | OR SBCCI PRODUCT APPROVALS FOR EXTERIOR | | | WINDOWS AND DOORS. MUST BE SPECIFIC FOR | | | EACH TYPE DOOR OR WINDOW USED. | | | NOTE:SITE SPECIFIC ENGINEERING IS ACCEPT | | | -ABLE FOR RELOCATED WINDOWS AND DOORS. | | | SUBMIT CITY OF WPB PRODUCT APPROVAL FORM | | | SIGNED AND SEALED BY ENGINEER CERTIFYING | | | PRODUCT AND REVIEWED & APPROVED BY THE | | | DESIGN PROFESSIONAL OF RECORD. | | | (SEE ATTACHED) | | | | | | 2)PROVIDE 2 CURRENT COPIES OF METRO-DADE | | | OR SBCCI PRODUCT APPROVALS FOR REQUIRED | | | MISSLE IMPACT PROTECTION (STORM PANELS), | | | KEY PLAN AND INSTALLATION SCHEDULE WITH | | | SPECIFIC ANCHORS TO BE USED. | | | | | | 3)SHEET S-1 OF PLANS SPECIFY SIMPSON | | | MPAHD HOLDOWNS @ EACH STUD. I DID NOT | | | SEE THIS PARTICULAR FASTENING DEVICE | | | LISTED IN THE SIMPSON PRODUCT CATALOG. | | | ARE YOU REFERRING TO HPAHD. | | | PLEASE CLARIFY. | | | | | | 4)PROVIDE 2 COMPLETED DESIGN COMPLIANCE | | | FORMS,SIGNED AND SEALED BY ENGINEER OR | | | ARCHITECT.(SEE ATTACHED) | | | | | | 5)PROVIDE 2 COPIES OF SOIL COMPACTION | | | TEST PRIOR TO 1ST INSPECTION. |
|