Notes
Date Text
2001-01-08 00:00:00DENIED
  
 1)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS FOR EXTERIOR
 WINDOWS AND DOORS. MUST BE SPECIFIC FOR
 EACH TYPE DOOR OR WINDOW USED.
 NOTE:SITE SPECIFIC ENGINEERING IS ACCEPT
 -ABLE FOR RELOCATED WINDOWS AND DOORS.
 SUBMIT CITY OF WPB PRODUCT APPROVAL FORM
 SIGNED AND SEALED BY ENGINEER CERTIFYING
 PRODUCT AND REVIEWED & APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD.
 (SEE ATTACHED)
  
 2)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS FOR REQUIRED
 MISSLE IMPACT PROTECTION (STORM PANELS),
 KEY PLAN AND INSTALLATION SCHEDULE WITH
 SPECIFIC ANCHORS TO BE USED.
  
 3)SHEET S-1 OF PLANS SPECIFY SIMPSON
 MPAHD HOLDOWNS @ EACH STUD. I DID NOT
 SEE THIS PARTICULAR FASTENING DEVICE
 LISTED IN THE SIMPSON PRODUCT CATALOG.
 ARE YOU REFERRING TO HPAHD.
 PLEASE CLARIFY.
  
 4)PROVIDE 2 COMPLETED DESIGN COMPLIANCE
 FORMS,SIGNED AND SEALED BY ENGINEER OR
 ARCHITECT.(SEE ATTACHED)
  
 5)PROVIDE 2 COPIES OF SOIL COMPACTION
 TEST PRIOR TO 1ST INSPECTION.