| 2001-01-08 00:00:00 | ****************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SUBMIT THE AIC RATING OF |
| | NEW MAIN AND PANEL. MAINS/PANELS ARE TO |
| | BE RATED FOR THE AVAILABLE FAULT CURRENT |
| | AS PER 110-9 AND 215-5 |
| | |
| | 2)NOTE: YOU SHOW A NEW 100 AMP MAIN AND |
| | PANEL? #6 FEEDING AND LOAD EXCEEDING |
| | THE RATINGOF #6? PLEASE CORRECT. |
| | |
| | 3)NOTE: PLEASE DOUBLE CHECK AS TO IF |
| | THERE ARE ANY OTHER A/C LOADS IN HOUSE |
| | AND IF SO SUBMIT ON LOAD CALCULATION. |
| | |
| | 4)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE |
| | AND OUTSIDE THE NEW SLEEPING ROOM AS PER |
| | NFPA-72 2-2.1.1.1. |
| | |
| | 5)NOTE: PLEASE ALSO NOTE THAT THE GROUND |
| | -ING ELECTRODE OF SERVICE NEEDS TO GO TO |
| | BLDG. STEEL OF NEW ADDITION. |
| | |
| | 6)NOTE: PLEASE SEE 210-70 FOR MEANS OF |
| | EGRESS LIGHTING REQ`D LEAVING SUN ROOM. |
| | CAN BE 4-WAY OR ??? |
| | |
| | 7)NOTE:ALSO PLEASE NOTE THAT THE SWITCH |
| | FOR MEANS OF EGRESS LIGHTING LEAVING |
| | MASTER BEDRROM NEEDS TO BE INSIDE THE |
| | BEDRROM. 210-70 |
| | |
| | 8)NOTE:PLEASE LIST ON THE PANEL SCHEDULE |
| | THE REQ`D BATH(S) CIRCUIT(S) AS PER |
| | 210-11-C-3 |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL 659-8096 EXT 8372 |