2001-01-08 00:00:00****************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT THE AIC RATING OF
 NEW MAIN AND PANEL. MAINS/PANELS ARE TO
 BE RATED FOR THE AVAILABLE FAULT CURRENT
 AS PER 110-9 AND 215-5
  
 2)NOTE: YOU SHOW A NEW 100 AMP MAIN AND
 PANEL? #6 FEEDING AND LOAD EXCEEDING
 THE RATINGOF #6? PLEASE CORRECT.
  
 3)NOTE: PLEASE DOUBLE CHECK AS TO IF
 THERE ARE ANY OTHER A/C LOADS IN HOUSE
 AND IF SO SUBMIT ON LOAD CALCULATION.
  
 4)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE THE NEW SLEEPING ROOM AS PER
 NFPA-72 2-2.1.1.1.
  
 5)NOTE: PLEASE ALSO NOTE THAT THE GROUND
 -ING ELECTRODE OF SERVICE NEEDS TO GO TO
 BLDG. STEEL OF NEW ADDITION.
  
 6)NOTE: PLEASE SEE 210-70 FOR MEANS OF
 EGRESS LIGHTING REQ`D LEAVING SUN ROOM.
 CAN BE 4-WAY OR ???
  
 7)NOTE:ALSO PLEASE NOTE THAT THE SWITCH
 FOR MEANS OF EGRESS LIGHTING LEAVING
 MASTER BEDRROM NEEDS TO BE INSIDE THE
 BEDRROM. 210-70
  
 8)NOTE:PLEASE LIST ON THE PANEL SCHEDULE
 THE REQ`D BATH(S) CIRCUIT(S) AS PER
 210-11-C-3
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372