| Notes |
| Date |
Text |
| 2001-10-04 00:00:00 | *****************PROVISO**************** | | | | | | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTOR WITH | | | NOTIFICATION TO ALARM/STROBE OR TO A | | | SUPERVISORY SIGNAL TO BE INDICATED AT A | | | CONSTANTLY ATTENDED LOCATION FOR | | | SYSTEMS WITH GREATER THAN 2,000 CFM OR | | | SYSTEMS SERVING AN AREA USED FOR EGRESS. | | | | | | PLEASE INDICATE ON PLANS UNITS REQUIRED | | | FOR FAN SHUT-DOWN OR UNITS UTILIZED IN | | | SMOKE EVAQ. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 EXT. | | | 8388 |
|