2001-01-08 00:00:00CALCULATIONS FOR SECONDARY(EMERGENCY)
 DRAINAGE SHALL BE BASED ON ON THE FLOW
 RATE IN FIGURE 1109.3 OF THE SPC.
 THE CALCULATIONS ARE UNCLEAR TO HOW YOU
 ARRIVED AT THE REQD.SIZES.SPC 1109.3, &
 APPENDIX "A"
  
 2)SHT.P2.4-8" LINE IS DRAINING INTO 6"
 LINE.STORM DRAIN ISOMETRIC SHOWS THE
 SAME.COMPLY W/SPC SEC.709.1.
  
 3)SLOPE OF PIPE SHALL BE NOTED ON THE
 PLANS.COUNTYWIDE AMENDMENTS TO SPC SEC.
  
 4)SUBMIT PIPING DETAILS FOR RELOCATED
 PLANTER DRAINS.NOTES ON P2.1 DON'T
 MENTION PLANTER DRAINS.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.