| 2001-01-08 00:00:00 | CALCULATIONS FOR SECONDARY(EMERGENCY) | | | DRAINAGE SHALL BE BASED ON ON THE FLOW | | | RATE IN FIGURE 1109.3 OF THE SPC. | | | THE CALCULATIONS ARE UNCLEAR TO HOW YOU | | | ARRIVED AT THE REQD.SIZES.SPC 1109.3, & | | | APPENDIX "A" | | | | | | 2)SHT.P2.4-8" LINE IS DRAINING INTO 6" | | | LINE.STORM DRAIN ISOMETRIC SHOWS THE | | | SAME.COMPLY W/SPC SEC.709.1. | | | | | | 3)SLOPE OF PIPE SHALL BE NOTED ON THE | | | PLANS.COUNTYWIDE AMENDMENTS TO SPC SEC. | | | | | | 4)SUBMIT PIPING DETAILS FOR RELOCATED | | | PLANTER DRAINS.NOTES ON P2.1 DON'T | | | MENTION PLANTER DRAINS.COUNTYWIDE | | | AMENDMENTS TO SPC SEC.104.2.1. | | | CALL 561-659-8096 EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|