| Plan Review Notes For Permit 00060837 |
| Permit Number |
00060837 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) WRONG CODE REFERENCE IN CODE ANALYSIS | | | BOX. SHOULD READ 1985 LIFE SAFETY CODE | | | INSTEAD ON 1997 LIFE SAFETY CODE. | | | 2) THE ATRIUM SMOKE CONTROL SYSTEM IS | | | TO BE ACTIVATED BY SMOKE DETECTORS, | | | THE SPRINKLER SYSTEM, THE FIRE ALARM | | | SYSTEM, AND MANUAL CONTROLS FOR THE | | | FIRE DEPARTMENT PER NFPA 101, THE LIFE | | | SAFETY CODE, 1985 EDITION, SECTION | | | 6-2.2.3.5, SECTION (G) | | | 3) THE ENTIRE ATRIUM IS TO MEET THE | | | REQUIREMENTS OF NFPA 101, THE LIFE | | | SAFETY CODE, 1985 EDITION, SECTION | | | 6-2.2.3.5, SECTION A-H. | | | 4) PLEASE PROVIDE TESTING INFORMATION | | | FOR THE ATRIUM SMOKE CONTROL SYSTEM. | | | 5) PLEASE PROVIDE A DRAWING ON WHAT THE | | | SMOKE CONTROL PANEL WILL LOOK LIKE. | | | 6) PLEASE PROVIDE FIRE ALARM SHOP | | | DRAWINGS FOR THE INSTALLATION OF NEW | | | FIRE ALARM EQUIPMENT. CUT SHEETS AND | | | WIRING DIAGRAM ARE TO BE SUBMITTED | | | UNDER SEPARATE PERMIT. | | | APPROVED PROVISO: |
|