2001-01-08 00:00:001) WRONG CODE REFERENCE IN CODE ANALYSIS
 BOX. SHOULD READ 1985 LIFE SAFETY CODE
 INSTEAD ON 1997 LIFE SAFETY CODE.
 2) THE ATRIUM SMOKE CONTROL SYSTEM IS
 TO BE ACTIVATED BY SMOKE DETECTORS,
 THE SPRINKLER SYSTEM, THE FIRE ALARM
 SYSTEM, AND MANUAL CONTROLS FOR THE
 FIRE DEPARTMENT PER NFPA 101, THE LIFE
 SAFETY CODE, 1985 EDITION, SECTION
 6-2.2.3.5, SECTION (G)
 3) THE ENTIRE ATRIUM IS TO MEET THE
 REQUIREMENTS OF NFPA 101, THE LIFE
 SAFETY CODE, 1985 EDITION, SECTION
 6-2.2.3.5, SECTION A-H.
 4) PLEASE PROVIDE TESTING INFORMATION
 FOR THE ATRIUM SMOKE CONTROL SYSTEM.
 5) PLEASE PROVIDE A DRAWING ON WHAT THE
 SMOKE CONTROL PANEL WILL LOOK LIKE.
 6) PLEASE PROVIDE FIRE ALARM SHOP
 DRAWINGS FOR THE INSTALLATION OF NEW
 FIRE ALARM EQUIPMENT. CUT SHEETS AND
 WIRING DIAGRAM ARE TO BE SUBMITTED
 UNDER SEPARATE PERMIT.