2001-01-08 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE SEE RISER/PANEL SCHEDULE
 ON E3.1,E2.4. EML1 SHOWN BEING 225A WITH
 250 OCP.?? ALSO CONTINUOUS LOADS TO BE
 SHOWN,,, AT 125%. (LIGHTING) ETC.
 PLEASE SEE THE LOAD SHOWN FOR EML1, THIS
 DOES NOT CORRELATE WITH LOAD SHOWN ON
 EML.?? IF MATCHED THEN LOAD WOULD GO
 OVER THE RATING OF 300 AMPS ON PANEL.
 PLEASE SHOW THE LOAD CALCULATIONS.
 PLEASE SHOW WHERE LOADS ARE COMING FROM.
  
  
 2)NOTE: SEE FOUNTAIN PUMP CONTROLLER ON
 E2.0. PLEASE SUBMIT CLARIFICATION ON
 PLANS WHERE FOUNTAIN LOCATION IS.
 PANEL SCHEDULE SHOWS AS BEING FUTURE??
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  