| Plan Review Notes For Permit 00060837 |
| Permit Number |
00060837 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE RISER/PANEL SCHEDULE | | | ON E3.1,E2.4. EML1 SHOWN BEING 225A WITH | | | 250 OCP.?? ALSO CONTINUOUS LOADS TO BE | | | SHOWN,,, AT 125%. (LIGHTING) ETC. | | | PLEASE SEE THE LOAD SHOWN FOR EML1, THIS | | | DOES NOT CORRELATE WITH LOAD SHOWN ON | | | EML.?? IF MATCHED THEN LOAD WOULD GO | | | OVER THE RATING OF 300 AMPS ON PANEL. | | | PLEASE SHOW THE LOAD CALCULATIONS. | | | PLEASE SHOW WHERE LOADS ARE COMING FROM. | | | | | | | | | 2)NOTE: SEE FOUNTAIN PUMP CONTROLLER ON | | | E2.0. PLEASE SUBMIT CLARIFICATION ON | | | PLANS WHERE FOUNTAIN LOCATION IS. | | | PANEL SCHEDULE SHOWS AS BEING FUTURE?? | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER/JAKE LEAHY | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|