2001-01-08 00:00:00SUBMIT COMPLETE STORM DRAINAGE ISOMETRIC
 FOR REVIEW.SHOW SQ.FOOT AREA DRAINED
 BY EACH DRAIN.COMPLY W/SPC SECS.AND
 TABLES 1108.1,1108.2.
  
 PROVIDE CALCULATIONS FOR SECONDARY
 (EMERGENCY)DRAINAGE.SUBMIT DETAILS OF
 SCUPPERS(LXW),OVERFLOW DRAINS AND SIZES,
 AND INCLUDE 1/2 THE AREA OF ANY VERTICAL
 WALLS IN YOUR CALCULATIONS PER SPC SEC.
 1108.3,1109.1,1109.2,1109.3,AND APPENDIX
 "A".
  
 INDICATE SLOPE OF PIPE ON THE PLANS.
  
 SHT.P-2.4-8"LINE IS DRAINING INTO A 6"
 LINE.COMPLY W/SPC SEC.709.1.
  
 SUBMIT PIPING DETAILS FOR RELOCATED
 PLANTER DRAINS.COUNTYWIDE AMENDMENTS TO
 SPC SEC.104.2.1.
  
 SUBMIT PLANS FOR FOUNTAIN IF COVERED
 UNDER THIS PERMIT.COUNTYWIDE AMENDMENTS
 TO SPC SEC.104.2.1.