| Plan Review Notes For Permit 00060837 |
| Permit Number |
00060837 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ****************DENIED****************** | | | | | | 1. PROVIDE INFORMATION SHOWING COMPLIANC | | | WITH 1997 SBC 414.4 RELATIVE TO HEIGHT | | | AND CU. FT. OF ATRIUM. EXAMPLE: HOW MUCH | | | EXHAUST AIR. LOCATION OF MECHANICAL | | | SUPPLY AIR @ 75% OF EXHAUST. PROVIDE | | | SEQUENCE OF OPERATION FOR SYSTEM. | | | 2. ALL SMOKE CONTROL EQUIPMENT SHALL BE | | | CONNECTED TO STANDBY POWER SYSTEM IN | | | ACCORDANCE WITH 412.7 | | | 3.PROVIDE INFORMATION ON OUTSIDE AIR PER | | | ASHRAE 62-89 | | | NOTE: COMPONENT PARTS OF RETURN AIR PLEN | | | UM AREAS ARE TO BE CONSTRUCTED ENTIRELY | | | OF NON- COMBUSTIBLE MATERIALS. PER 1997 | | | SMC 609 |
|