Plan Review Notes
Plan Review Notes For Permit 00060837
Permit Number 00060837
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001-NO FOUNTAINS SHOWN
 2-Q FIXTURES NOT SHOWN ON FIXTURE SCHEDU
 3-PANEL SCHEDULES DO NOT REFLECT CHANGES
 4-ALL LIGHTING LOADS SHOWN AT 100% NOT
 125%
 5-PLAQUES NEEDED ON SERVICE DISCONNECTS
 PER 230-2E AND 230-70B