Plan Review Notes
Plan Review Notes For Permit 00060828
Permit Number 00060828
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SHT.AA-INCORPORATE THE STANDARD PLUMBING
 CODE,1994 EDITION INTO CODE COMPLIANCE
 DATA LEGEND.COUNTYWIDE AMENDMENTS TO SPC
 SEC.101.2,101.4.6.,F.S.553.06.
 B)THE ADOPTED STANDARD GAS CODE IS THE
 1997 EDITION.
 C)THE ADOPTED ACCESSIBILITY CODE IS THE
 FLA.ACCESSIBILITY CODE FOR BUILDING
 CONSTRUCTION-OCTOBER 1997 EDITION.
  
 SUBMIT SQUARE FOOTAGE OF HABITABLE FLOOR
 SPACE FOR DETERMINATION OF MINIMUM
 SANITARY FACILITIES.SEE SPC SEC.407.1.3.
 FOR ALLOWED DEDUCTIBLE AREAS.
  
 A MINIMUM OF ONE DRINKING FOUNTAIN IS
 REQUIRED PER SPC TABLE 407.FOUNTAIN
 SHALL COMPLY W/FACBC SEC.4.1.3.(10)(A).
 PROVISIONS SHALL BE MADE FOR PEOPLE WHO
 HAVE TROUBLE BENDING OR STOOPING.
  
 DRESSING ROOM SHALL COMPLY W/FACBC SEC.
 4.35.4.(BENCH SHALL BE FIXED ALONG LONG
 WALL).
  
 SHT.A-8A-GRAB BARS ALONGSIDE WATER
 CLOSET SHALL BE A MIN.OF 42".DETAILS C &
 G NOTE 36".
  
 FLUSH CONTROLS FOR WATER CLOSETS SHALL
 BE LOCATED ON THE WIDE SIDE OF THE
 WATER CLOSET PER FACBC SEC.4.16.5.
  
 SHT.A-8A SHOWS HEIGHT OF ACCESSIBLE
 WATER CLOSETS AS 15".COMPLY W/FACBC SEC.
 4.16.3.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7.SUPPLY FIXED LADDER
 OR RELOCATE EWH TO FLOOR.
  
 WATER CLOSETS NOT PERMITTED ON WET VENTS
 PER COUNTYWIDE AMENDMENTS SEC.911.1.1.
 OR COMPLY W/SPC SEC.914.1 FOR CIRCUIT
 AND LOOP VEN SYSTEM IF THAT IS THE
 INTENT.