| 2001-01-08 00:00:00 | *************DENIED******************** | | | | | | 1. 1997 SMC 610 REQUIRES FIRE DAMPERS AT | | | ALL PENETRATIONS OF RATED WALLS | | | 2. SMC 610.6 REQUIRES THAT THE SPECIFIC | | | LOCATION AND INSTALLATION DETAILS OF EA. | | | FIRE DAMPER SHALL BE SHOWN AND PROPERLY | | | IDENTIFIED ON THE BUILDING PLANS BY THE | | | DESIGNER | | | 3. PROVIDE ENERGY EFFIECIENCY RATING OF | | | AHU. | | | 4. OUTSIDE AIR PER ASHRAE 62-89 REQUIRED | | | 5. PROVIDE AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2 |
|