| Plan Review Notes For Permit 00060740 |
| Permit Number |
00060740 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | A DRINKING FOUNTAIN IS REQD.PER TABLE | | | 407 OF THE SPC.FOUNTAIN SHALL COMPLY W/ | | | FACBC SEC.4.1.3.(10)(A).PROVISIONS SHALL | | | BE MADE FOR PEOPLE WHO HAVE TROUBLE | | | BENDING OR STOOPING. | | | | | | SHOW DRINKING FOUNTAIN ON WATER AND | | | SANITARY RISER.COUNTYWIDE AMENDMENTS TO | | | SPC SEC.104.2.1.SHOW LENGTH AND WIDTH OF | | | TOILET ROOMS.COMPLY W/FACBC SEC.4.16.2. | | | | | | WALLS IN TOILET ROOMS SHALL BE | | | NONABSORBENT TO A HEIGHT OF 4'PER SBC | | | SEC.1204.2. | | | | | | PIPE INSULATION SHALL COMPLY W/FEC | | | TABLE 4-11.SEE SHT.MP-1. | | | | | | SUBMIT MANUF.SHEETS ON EWH.WATER HEATER | | | SHALL BE LISTED PER SPC SEC.503.3. | | | | | | SIZE THE SOIL AND WASTE STACKS ON THE | | | SANITARY RISER. |
|