Plan Review Notes
Plan Review Notes For Permit 00060740
Permit Number 00060740
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00A DRINKING FOUNTAIN IS REQD.PER TABLE
 407 OF THE SPC.FOUNTAIN SHALL COMPLY W/
 FACBC SEC.4.1.3.(10)(A).PROVISIONS SHALL
 BE MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.
  
 SHOW DRINKING FOUNTAIN ON WATER AND
 SANITARY RISER.COUNTYWIDE AMENDMENTS TO
 SPC SEC.104.2.1.SHOW LENGTH AND WIDTH OF
 TOILET ROOMS.COMPLY W/FACBC SEC.4.16.2.
  
 WALLS IN TOILET ROOMS SHALL BE
 NONABSORBENT TO A HEIGHT OF 4'PER SBC
 SEC.1204.2.
  
 PIPE INSULATION SHALL COMPLY W/FEC
 TABLE 4-11.SEE SHT.MP-1.
  
 SUBMIT MANUF.SHEETS ON EWH.WATER HEATER
 SHALL BE LISTED PER SPC SEC.503.3.
  
 SIZE THE SOIL AND WASTE STACKS ON THE
 SANITARY RISER.