| Plan Review Notes For Permit 00060740 |
| Permit Number |
00060740 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE CHECK THE AVAILABLE FAULT | | | FROM TRANSFORMER TO PANEL 'C'.ALSO YOU | | | ARE SHOWING AIC RATING AT 24,000?? THIS | | | IS NOT A STANDARD SIZE, PLEASE CORRECT. | | | | | | 2)NOTE: PLEASE SHOW THE GROUNDING BOND | | | TO COLD WATER PIPE. | | | | | | | | | 3)NOTE: PLEASE NOTE OUT SPACING TO MEET | | | LOCAL CODE EVERY 20`FOR STORAGE AND | | | OFFICE RETAIL EVERY 12` OF UNENCUMERED | | | WALL SPACE. 210-50 | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW.IF THERE ARE ANY QUESTIONS | | | PLEASE CALL DEWEY V PALMER 561-659-8096 | | | EXT 8372 |
|