Plan Review Notes
Plan Review Notes For Permit 00060740
Permit Number 00060740
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE CHECK THE AVAILABLE FAULT
 FROM TRANSFORMER TO PANEL 'C'.ALSO YOU
 ARE SHOWING AIC RATING AT 24,000?? THIS
 IS NOT A STANDARD SIZE, PLEASE CORRECT.
  
 2)NOTE: PLEASE SHOW THE GROUNDING BOND
 TO COLD WATER PIPE.
  
  
 3)NOTE: PLEASE NOTE OUT SPACING TO MEET
 LOCAL CODE EVERY 20`FOR STORAGE AND
 OFFICE RETAIL EVERY 12` OF UNENCUMERED
 WALL SPACE. 210-50
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW.IF THERE ARE ANY QUESTIONS
 PLEASE CALL DEWEY V PALMER 561-659-8096
 EXT 8372