| Plan Review Notes For Permit 00060672 |
| Permit Number |
00060672 |
|
| Review Stop |
P |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)A MIN.OF 4 WATER CLOSETS ARE REQD.IN | | | THE WOMEN'S RESTROOM PER THE OCCUPANT | | | LOAD AND SPC TABLE 407.COMPLY W/FLA. | | | STATUTE 553.141(3)POTTY PARITY. | | | | | | 2)WATER SUPPLY CONTROL SHALL COMPLY W/ | | | SPC SEC.610.4.1,610.4.2. | | | | | | 3)SHT.P-2,P-6-GAS MAIN FROM THE METER | | | SHALL BE SIZED 3" PER SGC TABLE 305.4(A) | | | YOUR NOTE STATES 3" BUT THE DRAWING IS | | | STILL WRONG! | | | | | | 4)ALL FLOOR DRAINS IN TOILET ROOMS SHALL | | | BE 3"PER SPC SEC.409.4.1.1. | | | | | | 5)SHT.P-5-VACUUM RELIEF VALVE IS NOT | | | LOCATED CORRECTLY.VALVE SHALL BE IN- | | | STALLED ON THE WATER SUPPLY OF THE COLD | | | WATER,NOT ON THE HOT WATER SIDE. |
|