Plan Review Notes
Plan Review Notes For Permit 00060672
Permit Number 00060672
Review Stop P
Sequence Number 4
Notes
Date Text
2001-01-08 00:00:001)SHT.P-3-ALL FLOOR DRAINS LOCATED IN
 TOILET ROOMS SHALL BE 3" PER SPC SEC.
 409.4.1.1.
  
 2)SHT.P-3-(BAR AREA)-DESIGN OF PLUMBING
 SHALL COMPLY W/SPC SEC.921 FOR WASTE
 AND VENT SYSTEM IF THAT IS THE INTENT.
  
 3)NOTE THE OCCUPANT LOAD ON THE PLANS
 ACCORDING TO THE TOTAL NUMBER OF SEATS
 AND SEATING SPACE AT BOOTHS AND BARS.
 COMPLY W/TABLE 407 OF SPC.SEE SBC TABLE
 1003.1 FOOTNOTE #1 FOR BAR AND BOOTH
 REQS.
  
 4)MINIMUM NUMBER OF REQD.SANITARY
 FACILITIES SHALL BE BASED ON ABOVE REQS.
  
 5)WATER SUPPLY CONTROL SHALL COMPLY W/
 SPC SEC.610.4.1.,610.4.2.
  
 6)SHT.P-6-GAS MAIN FROM METER SHALL BE
 SIZED A MIN.OF 3"PER SGC TABLE 305.4(A).
  
 7)SHT.A1.1-A MIN.OF 4 WATER CLOSETS ARE
 REQD.IN THE WOMEN'S RESTROOM PER SPC
 TABLE 407.ADDITIONAL PLUMBING FIXTURES
 MAY BE REQD.IN BOTH RESTROOMS PENDING
 CORRECT OCCUPANT LOAD COUNT.
  
 8)NUMBER OF SANITARY FACILITIES SHALL
 COMPLY W/FLA.STATUTE 553.141.(POTTY
 PARITY).