| Plan Review Notes For Permit 00060672 |
| Permit Number |
00060672 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************PROVISO **************** | | | | | | 1)NOTE: LOAD CALCULATIONS NEED TO BE | | | COMPLETED. SHOW ALL CONTINUOUS LOADS | | | FIGURED AT 125% (LIGHTING,LARGEST MOTOR | | | ETC). PLEASE SHOW ALL THE FINAL LOADS | | | IN AMPS FOR EACH PANEL AND MDP.. | | | | | | 2)NOTE: PLEASE CHANGE COVER SHEET TO | | | REFLECT THE "99" NEC. | | | | | | PLEASE REVISE AND SUBMIT THE ABOVE | | | INFORMATION FOR REVIEW BEFORE ROUGH | | | ELECTRICAL INSPECTION IS CALLED IN. IF | | | THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | | | | 561-659-8096 EXT 8372 |
|