| 2001-01-08 00:00:00 | ADDITIONAL PLUMBING FIXTURES ARE REQD.IN |
| | THE MEN'S AND WOMENS RESTROOMS PER TABLE |
| | 407 OF THE SPC BASED ON NUMBER OF SEATS. |
| | BATHROOMS SHALL ALSO COMPLY W/FLA.STAT. |
| | 555.141.(POTTY PARITY). |
| | |
| | NUMBER AND LOCATION OF PLUMBING FIXTURES |
| | IN THE MEN'S ROOM ARE NOT TYPICAL |
| | THROUGHOUT THE PLANS.(TWO URINALS ARE |
| | SHOWN ON SOME SHEETS AND ONE IS SHOWN ON |
| | OTHERS.)COUNTYWIDE AMENDMENTS TO SPC |
| | SEC.104.2.1. |
| | |
| | PLANS STILL SHOW THE VENTS FOR THE FLOOR |
| | DRAINS OFFSETTING HORIZONTALLY BELOW |
| | THE SLAB.SHOW COMPLIANCE W/SPC SEC. |
| | 906.2.1.(NOTES ARE NOT ACCEPTABLE.) |
| | |
| | SUBMIT COMPLETE GAS RISER DIAGRAM FOR |
| | REVIEW.SHOW DISTANCE TO MOST REMOTE |
| | OUTLET,PIPE SIZES,,PIPE MATERIAL,BTU |
| | LOAD OF EACH APPLIANCE,CALCULATIONS FOR |
| | COMBUSTION AIR,DETAILS ON VENT AND VENT- |
| | MATERIALS,ETC... |
| | |
| | GAS CONTROLS SHALL COMPLY W/NFPA 5.5.4. |
| | SHOW COMPLIANCE ON THE GAS RISER. |
| | |
| | INSTALLATION OF CLEANOUTS IN THE DRAIN- |
| | AGE SYSTEM SHALL COMPLY W/SPC SEC.710.2. |
| | |
| | VACUUM RELIEF VALVE IS REQUIRED ON THE |
| | COLD WATER SUPPLY TO THE WATER HEATERS |
| | PER SPC SEC.507.1.2.(THE PLANS SHOW A |
| | CHECK VALVE,NOT A VACUUM RELIEF VALVE.) |
| | |
| | THE U.L ASSEMBLY NUMBER FOR THE FIRE |
| | SAFING DETAIL OF PIPE PENETRATIONS SHALL |
| | BE ON THE PLANS.COUNTYWIDE AMENDMENTS TO |
| | SPC SEC.104.2.1. |
| | |
| | SHT.CS-1-REVISE EDITION OF STANDARD GAS |
| | CODE TO READ 1997 EDITION. |
| | |
| | SHT.CS-1-BUILDING SUMMARY-SANITARY |
| | FACILITIES CANNOT BE BASED ON 50% MALES |
| | AND 50% FEMALES.TABLE 407 OF THE SPC |
| | LISTS SANITARY FACILITIES FOR TOTAL |
| | PERSONS. |
| | |
| | EMPLOYEE TOILET ROOM SHALL BE HANDICAP |
| | ACCESSIBLE PER FACBC SEC.4.1.3.(11) |
| | |
| | FLUSH CONTROLS IN ACCESSIBLE STALLS AND |
| | TOILET ROOMS SHALL BE LOCATED ON THE |
| | WIDE SIDE PER FACBC SEC.4.16.5. |
| | |
| | CONDENSATE DRAINS CANNOT DISCHARGE TO |
| | FLOOR SINK.DISPOSAL SHALL COMPLY W/SMC |
| | SEC.304.8.3. |
| | |
| | SHT.P-3-FLOOR SINK SHALL NOT EXCEED |
| | DISTANCE FROM VENT AS MANDATED IN SPC |
| | SEC.908.1.(SEE F.S.BY MENS R.R.) |
| | |
| | DRY VENTS NOT PERMITTED PER SPC SEC. |
| | 906.2.1.(SEE VENT BY WINE ROOM) |