2001-01-08 00:00:00*********DENIED*************************
 1) OUTSIDE AIR CALCULATIONS DO NOT
 COMPLY WITH ASHRAE 62-89. EX:
 SMOKING LOUNGE CALLS FOR 60 CFM PER
 PERSON THERE IS NO EQUIVELANT PER SQ FT
 VALUE TO USE. SMOKING DINING @ 20 CFM
 PER PERSON WOULD BE 1160 @ 58 PEOPLE
 AND LOUNGE @ 59 PEOPLE = 3540 CFM TOTAL
 OUTSIDE AIR FOR AC 3 = 4700 CFM. VALUE
 SUPPIED = 2310 CFM NOT PER REQUIREMENT
 PROVIDE OUTSIDE AIR PER ASHRAE 62-89
 2) GREASE EXHAUST DUCT REQUIRES 1" PER
 12" SLOPE TOWARD HOOD MIN. PER 1997 SMC
 505.4 PROVIDE ELEVATION SHOWING SPACE
 AVAIABILITY FOR LENGTH OF RUN