| Plan Review Notes For Permit 00060672 |
| Permit Number |
00060672 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *********DENIED************************* | | | 1) OUTSIDE AIR CALCULATIONS DO NOT | | | COMPLY WITH ASHRAE 62-89. EX: | | | SMOKING LOUNGE CALLS FOR 60 CFM PER | | | PERSON THERE IS NO EQUIVELANT PER SQ FT | | | VALUE TO USE. SMOKING DINING @ 20 CFM | | | PER PERSON WOULD BE 1160 @ 58 PEOPLE | | | AND LOUNGE @ 59 PEOPLE = 3540 CFM TOTAL | | | OUTSIDE AIR FOR AC 3 = 4700 CFM. VALUE | | | SUPPIED = 2310 CFM NOT PER REQUIREMENT | | | PROVIDE OUTSIDE AIR PER ASHRAE 62-89 | | | 2) GREASE EXHAUST DUCT REQUIRES 1" PER | | | 12" SLOPE TOWARD HOOD MIN. PER 1997 SMC | | | 505.4 PROVIDE ELEVATION SHOWING SPACE | | | AVAIABILITY FOR LENGTH OF RUN |
|