2001-01-08 00:00:00SUBMIT OCCUPANT LOAD BASED UPON 40 SQ.
 FT.PER PERSON PER TABLE 407 OF SPC.SEE
 SPC SEC.407.1.3.FOR ALLOWED DEDUCTIBLE
 AREAS.
  
 URINAL IN MEN'S ROOM IS LOCATED IN LINE
 OF SIGHT FROM CORRIDOR.FIXTURES SHALL BE
 SUITABLY SCREENED FOR PRIVACY PER SPC
 404.3.
  
 NUMBER AND LOCATION OF PLUMBING FIXTURES
 ON SHT.PR-1 DOESN'T CORRELATE W/ARCH.
 DRAWINGS.CLARIFY.COUNTYWIDE AMENDMENTS
 TO SPC 104.2.1.
  
 DISHWASHER SHALL DISCHARGE TO THE
 SANITARY SYSTEM PER CITY OF WEST PALM
 BEACH ORDINANCE.
  
 INDICATE IF GREASE TRAP/GREASY WASTE
 SYSTEM IS NEW OR EXISTING.SUBMIT DETAILS
 ON GREASE TRAP.GREASE RECOVERY UNITS ARE
 NOT PERMITTED.SPC 1004.2
  
 INDIRECT WASTES SHALL DISCHARGE TO FLOOR
 SINKS PER 807.1.2, 807.1.3.
  
 THE DISCHARGE FROM ALL SINKS,INDIRECT
 WASTES,ETC.(EXCEPT THE DISHWASHER)SHALL
 DISCHARGE TO THE GREASY WASTE SYSTEM.
 SPC SEC.1004.4
  
 SUBMIT APPROVAL FROM CITY OF WPB
 UTILITIES FOR GREASE TRAP.
  
 2-WAY CLEANOUTS ARE REQD.ON THE INLET
 AND OUTLET OF THE GREASE INTERCEPTOR PER
 SPC SEC.710.4.
  
 SHT.P-3-VENTS FOR FLOOR DRAINS SHALL
 6"ABOVE FLOOD LEVEL RIM PRIOR TO OFF-
 SETTING HORIZONTALLY PER SPC SEC.906.2.1
  
 SUBMIT COMPLETE GAS RISER DIAGRAM FOR
 REVIEW.SHOW DISTANCE TO MOST REMOTE
 OUTLET,PIPE SIZES,PIPE MATERIAL,BTU LOAD
 OF EACH APPLIANCE, ETC.COMPLY W/SGC SEC.
 305.4.
  
 GAS CONTROLS SHALL COMPLY W/NFPA 54 SEC.
 5.5.4.
  
 LOCATION OF GAS VALVES FOR EQUIPMENT
 SHALL BE READILY ACCESSIBLE PER SGC SEC.
 310.1.
  
 PLEASE SUBMIT A LEGIBLE AND EXPANDED
 SANITARY ISOMETRIC FOR REVIEW.(SEE REST-
 ROOM AREAS.)COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 BACKFLOW PREVENTERS ARE REQD.ON THE
 CARBONATION EQUIP PER SPC SEC.606.1.
  
 SHT.P-6-NOTE #8-INSTALLATION OF CLEAN-
 OUTS IN THE DRAINAGE SYSTEM SHALL COMPLY
 W/SPC SEC.710.2.4.
  
 SUBMIT MANUF.SHEETS FOR COMPONENTS OF
 THE 2# SYSTEM.SGC SEC.1006.
  
 A VACUUM RELIEF VALVE IS REQD.ON THE
 COLD WATER SUPPLY TO THE WATER HEATERS
 PER SPC SEC.507.1.2.
  
 SUBMIT U.L. ASSEMBLY NUMBER FOR FIRE
 SAFING DETAIL OF PIPE PENETRATIONS THRU
 RATED WALLS.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.4.
  
 NUMBER OF REQUIRED SANITARY FACILITIES
 SHALL COMPLY W/FLA.STATUTE 553.141.
 (POTTY PARITY)