| 2001-01-08 00:00:00 | SUBMIT OCCUPANT LOAD BASED UPON 40 SQ. |
| | FT.PER PERSON PER TABLE 407 OF SPC.SEE |
| | SPC SEC.407.1.3.FOR ALLOWED DEDUCTIBLE |
| | AREAS. |
| | |
| | URINAL IN MEN'S ROOM IS LOCATED IN LINE |
| | OF SIGHT FROM CORRIDOR.FIXTURES SHALL BE |
| | SUITABLY SCREENED FOR PRIVACY PER SPC |
| | 404.3. |
| | |
| | NUMBER AND LOCATION OF PLUMBING FIXTURES |
| | ON SHT.PR-1 DOESN'T CORRELATE W/ARCH. |
| | DRAWINGS.CLARIFY.COUNTYWIDE AMENDMENTS |
| | TO SPC 104.2.1. |
| | |
| | DISHWASHER SHALL DISCHARGE TO THE |
| | SANITARY SYSTEM PER CITY OF WEST PALM |
| | BEACH ORDINANCE. |
| | |
| | INDICATE IF GREASE TRAP/GREASY WASTE |
| | SYSTEM IS NEW OR EXISTING.SUBMIT DETAILS |
| | ON GREASE TRAP.GREASE RECOVERY UNITS ARE |
| | NOT PERMITTED.SPC 1004.2 |
| | |
| | INDIRECT WASTES SHALL DISCHARGE TO FLOOR |
| | SINKS PER 807.1.2, 807.1.3. |
| | |
| | THE DISCHARGE FROM ALL SINKS,INDIRECT |
| | WASTES,ETC.(EXCEPT THE DISHWASHER)SHALL |
| | DISCHARGE TO THE GREASY WASTE SYSTEM. |
| | SPC SEC.1004.4 |
| | |
| | SUBMIT APPROVAL FROM CITY OF WPB |
| | UTILITIES FOR GREASE TRAP. |
| | |
| | 2-WAY CLEANOUTS ARE REQD.ON THE INLET |
| | AND OUTLET OF THE GREASE INTERCEPTOR PER |
| | SPC SEC.710.4. |
| | |
| | SHT.P-3-VENTS FOR FLOOR DRAINS SHALL |
| | 6"ABOVE FLOOD LEVEL RIM PRIOR TO OFF- |
| | SETTING HORIZONTALLY PER SPC SEC.906.2.1 |
| | |
| | SUBMIT COMPLETE GAS RISER DIAGRAM FOR |
| | REVIEW.SHOW DISTANCE TO MOST REMOTE |
| | OUTLET,PIPE SIZES,PIPE MATERIAL,BTU LOAD |
| | OF EACH APPLIANCE, ETC.COMPLY W/SGC SEC. |
| | 305.4. |
| | |
| | GAS CONTROLS SHALL COMPLY W/NFPA 54 SEC. |
| | 5.5.4. |
| | |
| | LOCATION OF GAS VALVES FOR EQUIPMENT |
| | SHALL BE READILY ACCESSIBLE PER SGC SEC. |
| | 310.1. |
| | |
| | PLEASE SUBMIT A LEGIBLE AND EXPANDED |
| | SANITARY ISOMETRIC FOR REVIEW.(SEE REST- |
| | ROOM AREAS.)COUNTYWIDE AMENDMENTS TO SPC |
| | SEC.104.2.1. |
| | |
| | BACKFLOW PREVENTERS ARE REQD.ON THE |
| | CARBONATION EQUIP PER SPC SEC.606.1. |
| | |
| | SHT.P-6-NOTE #8-INSTALLATION OF CLEAN- |
| | OUTS IN THE DRAINAGE SYSTEM SHALL COMPLY |
| | W/SPC SEC.710.2.4. |
| | |
| | SUBMIT MANUF.SHEETS FOR COMPONENTS OF |
| | THE 2# SYSTEM.SGC SEC.1006. |
| | |
| | A VACUUM RELIEF VALVE IS REQD.ON THE |
| | COLD WATER SUPPLY TO THE WATER HEATERS |
| | PER SPC SEC.507.1.2. |
| | |
| | SUBMIT U.L. ASSEMBLY NUMBER FOR FIRE |
| | SAFING DETAIL OF PIPE PENETRATIONS THRU |
| | RATED WALLS.COUNTYWIDE AMENDMENTS TO SPC |
| | SEC.104.2.4. |
| | |
| | NUMBER OF REQUIRED SANITARY FACILITIES |
| | SHALL COMPLY W/FLA.STATUTE 553.141. |
| | (POTTY PARITY) |