| Plan Review Notes For Permit 00060672 |
| Permit Number |
00060672 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************DENIED******************** | | | PLEASE PROVIDE ADDITIONAL INFORMATION | | | FOR REVIEW: | | | 1. PROVIDE OUTSIDE AIR SCHEDULE PER | | | ASHRAE 62-89 | | | 2PROVIDE ROOF PLAN SHOWING TERMINATION | | | OF GREASE DUCT, OUTSIDE AIR INTAKE, FLUE | | | AND RTU'S | | | 3. PROVIDE DETAIL SHOWING VERTICAL RUN | | | OF FLUE, GREASE DUCT, ETC FOR REVIEW | | | 4. PROVIDE ENERGY EFFICIENCY RATING PER | | | ENERGY EFFICIENCY CODE FOR BUILDING | | | CONSTRUCTION (STATE OF FLORIDA) 1997 ED | | | NOTE: SEPARATE PERMITS REQUIRED FOR HOOD | | | COOLERS, FIRE SUPPRESSION. SUBMIT PLANS | | | AT TIME OF MECHANICAL PERMIT APPLICATION | | | FOR ABOVE |
|