Plan Review Notes
Plan Review Notes For Permit 00060672
Permit Number 00060672
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT AICRATINGS FOR
 ALL MAINS/PANELS. ALL EQUIPMENT MUST BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110-9/215-5
  
 2)NOTE: PLEASE SUBMIT AND SHOW THE
 ENTIRE LOAD CALCULATION FOR EAACH PANEL
 AND THE MDP/MAIN. PLEASE SHOW ALL LOADS
 THAT ARE CONTINUOUS AT 125%(LIGHTING)ETC
 AND 25% FOR LARGEST MOTOR LOAD.
  
 3)NOTE:PLEASE SHOW THE GROUNDING SYSTEM.
 COLD WATER/EXISTING BLDG. GROUND ATTACH.
 215-5
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL DEWEY PALMER 561-659-8096
 EXT 8372