| Plan Review Notes For Permit 00060672 |
| Permit Number |
00060672 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SUBMIT AICRATINGS FOR | | | ALL MAINS/PANELS. ALL EQUIPMENT MUST BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110-9/215-5 | | | | | | 2)NOTE: PLEASE SUBMIT AND SHOW THE | | | ENTIRE LOAD CALCULATION FOR EAACH PANEL | | | AND THE MDP/MAIN. PLEASE SHOW ALL LOADS | | | THAT ARE CONTINUOUS AT 125%(LIGHTING)ETC | | | AND 25% FOR LARGEST MOTOR LOAD. | | | | | | 3)NOTE:PLEASE SHOW THE GROUNDING SYSTEM. | | | COLD WATER/EXISTING BLDG. GROUND ATTACH. | | | 215-5 | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL DEWEY PALMER 561-659-8096 | | | EXT 8372 |
|