| Plan Review Notes For Permit 00060672 |
| Permit Number |
00060672 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1. LETTER FROM SPECIAL INSPECTOR | | | RELEASINF SPACE. | | | 2. FIRE SPRINKLER PERMIT TO BE ISSUED | | | PRIOR TO ISSUANCE OF BUILDING PERMIT. | | | 3. EXTERIOR GLAZING PROVIDE PRODUCT | | | APPROVAL INFORMATION, METRO DADE COUNTY | | | OR STANDARD BUILDING CODE 1997, SSTD1297 | | | 4. SHEET A-5.1, SECTION 5 ALL PLYWOOD | | | AND WOOD FRAMING TO BE PRESSURE TREATED | | | FIR RETARDANT LUMBER. SEE 1997 SBC | | | CHAPTERS 6 AND 7, FOR TYPE 2 | | | CONSTRUCTION. | | | 5. SHEET A5.5 OPEANINGSUNDER STAIRS | | | SHALL BE FIRE RATED IF WITHIN 10 FEET | | | SEE 1997 SBC CHAPTERS 6, 7 AND 10. | | | | | | | | | 7. SIGNS REQUIRE SEPERATE PERMITS. |
|