Plan Review Notes
Plan Review Notes For Permit 00060472
Permit Number 00060472
Review Stop B
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00TRUSSES
  
 DENIED
  
 1)PLEASE INDICATE THE TRUSS ANCHORS THAT
 ARE TO BE USED WHERE NONE IS SPECIFIED.
  
 2)THERE IS NO DETAIL C OR C1 SHOWN ON
 SHEET A-8.
  
 3)TRUSS GTD HAS NO ANCHOR INDICATED FOR
 THE LEFT SIDE WHICH TRUSS DRAWINGS SHOW
 7097# OF UPLIFT. STEEL COLUMN IS NOT
 INDICATED ON REVISED DRAWING,UPLIFT AND
 BEARING CAPACITY INDICATED ON TRUSS
 DRAWING EXCEED THOSE LISTED ON SHEET A-8
  
 4)TRUSS GTK HAS UPLIFTS OF 1063# AND
 1713# WITH NO CONNECTORS SPECIFIED.
  
 5)TRUSS GTC IS INDICATED AS HAVING AN
 A-3 ANCHOR. THIS SHOULD BE A STEEL
 COLUMN.
  
 6)TRUSS HB1 IS INDICATED AS HAVING AN
 A-3 ANCHOR AT WOOD FRAME INTERIOR
 BEARING WALL. THIS ANCHOR IS DESIGNED
 FOR EMBEDMENT INTO CONCRETE.
  
 7)A-3 ANCHOR (UPLIFT 2900#)IS INDICATED
 FOR TRUSS GTH1 TRUSS ENGINEERING
 REQUIRES 4652# OF UPLIFT.
  
 8)A-3 ANCHOR (UPLIFT 2900#)IS INDICATED
 FOR TRUSS GTG1 TRUSS ENGINEERING
 REQUIRES 3874# OF UPLIFT.
  
 9)TRUSS ENGINEERING CALLS FOR 1199# OF
 UPLIFT FOR TRUSS HE1,THIS TRUSS IS TO
 BE ANCHORED TO FGTM TRUSSES AT COVERED
 ENTRY. EITHER THE ARCHITECT OR TRUSS
 ENGINEER NEEDS TO INDICATE CONNECTORS
 FOR THESE TRUSSES AND THE SIMILAR ONES
 LOCATED AT REAR PORCH.
  
 10)PLEASE STEEL COLUMNS TO ENSURE THEY
 HAVE ADEQUATE BEARING AREA FOR THE
 TRUSSES THEY SUPPORT.
  
 PLEASE HAVE ARCHITECT ADDRESS THESE
 ITEMS. IF YOU HAVE ANY QUESTIONS PLEASE