Plan Review Notes
Plan Review Notes For Permit 00060472
Permit Number 00060472
Review Stop B
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00TRUSS LAYOUT AND TRUSS DRAWINGS
 ****************DENIED******************
  
 1)DUE TO THE AMOUNT OF CHANGES BETWEEN
 THE ARCHITECT'S ROOF FRAMING PLAN AND
 THE ENGINEERED TRUSS LAYOUT, PLEASE
 PROVIDE A REVISED ROOF FRAMING PLAN
 (SHEET A-7) WHICH ADDRESS THE CHANGES
 AND SPECIFIES REQUIRED CONNECTORS AND
 UPLIFTS.
  
 2)CONNECTION DETAIL(C AND C1 ON A-8)AS
 INDICATED ON SHEET A-7 ARE NOT SHOWN OR
 ARE MISIDENTIFIED AS DETAIL B AND B-1.
 PLEASE CLARIFY.
  
 3)PLEASE INDICATE SPECIFIC CONNECTORS
 AND UPLIFT CAPACITY OF TRUSS TO GIRDER
 CONNECTIONS AT ENTRY FOYER AND COVERED
 PORCH.
  
 4)THE UPLIFT LOADS INDICATED ON THE
 TRUSS DRAWING EXCEED THE VALUES OF THE
 CONNECTORS SPECIFIED FOR TRUSS GTD.
  
 5)DETAIL 2 ON A-8 FOR INTERIOR BEARING
 WALLS SPECIFIES SEMCO RTP 18816 WHICH
 ARE RATED AT 1172# UPLIFT TRUSS DRAWINGS
 LIST UPLIFT AT 1204#.
  
 6)TRUSS LAYOUT SHOWS FGTM1 AS A THREE
 MEMBER TRUSS, HAS (2M) TWO MEMBER ? AND
 TRUSS DRAWINGS INDICATE 1 PLY. PLEASE
 CLARIFY.
  
 7)PLEASE HAVE DESIGNER OF RECORD REVIEW
 TRUSS DRAWINGS FOR DISCREPANCIES IN
 ADDITION TO HIS REVIEW OF THE LAYOUT.
  
 8)PLEASE CLARIFY SPECIFIC CONNECTOR AND
 UPLIFT RATING TO BE USED ON TRUSSES NOT
 SPECIFICALLY NOTED.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 ROBERT MCDOUGAL AT 659-8096 EXT.8202.