| 2001-01-08 00:00:00 | TRUSS LAYOUT AND TRUSS DRAWINGS |
| | ****************DENIED****************** |
| | |
| | 1)DUE TO THE AMOUNT OF CHANGES BETWEEN |
| | THE ARCHITECT'S ROOF FRAMING PLAN AND |
| | THE ENGINEERED TRUSS LAYOUT, PLEASE |
| | PROVIDE A REVISED ROOF FRAMING PLAN |
| | (SHEET A-7) WHICH ADDRESS THE CHANGES |
| | AND SPECIFIES REQUIRED CONNECTORS AND |
| | UPLIFTS. |
| | |
| | 2)CONNECTION DETAIL(C AND C1 ON A-8)AS |
| | INDICATED ON SHEET A-7 ARE NOT SHOWN OR |
| | ARE MISIDENTIFIED AS DETAIL B AND B-1. |
| | PLEASE CLARIFY. |
| | |
| | 3)PLEASE INDICATE SPECIFIC CONNECTORS |
| | AND UPLIFT CAPACITY OF TRUSS TO GIRDER |
| | CONNECTIONS AT ENTRY FOYER AND COVERED |
| | PORCH. |
| | |
| | 4)THE UPLIFT LOADS INDICATED ON THE |
| | TRUSS DRAWING EXCEED THE VALUES OF THE |
| | CONNECTORS SPECIFIED FOR TRUSS GTD. |
| | |
| | 5)DETAIL 2 ON A-8 FOR INTERIOR BEARING |
| | WALLS SPECIFIES SEMCO RTP 18816 WHICH |
| | ARE RATED AT 1172# UPLIFT TRUSS DRAWINGS |
| | LIST UPLIFT AT 1204#. |
| | |
| | 6)TRUSS LAYOUT SHOWS FGTM1 AS A THREE |
| | MEMBER TRUSS, HAS (2M) TWO MEMBER ? AND |
| | TRUSS DRAWINGS INDICATE 1 PLY. PLEASE |
| | CLARIFY. |
| | |
| | 7)PLEASE HAVE DESIGNER OF RECORD REVIEW |
| | TRUSS DRAWINGS FOR DISCREPANCIES IN |
| | ADDITION TO HIS REVIEW OF THE LAYOUT. |
| | |
| | 8)PLEASE CLARIFY SPECIFIC CONNECTOR AND |
| | UPLIFT RATING TO BE USED ON TRUSSES NOT |
| | SPECIFICALLY NOTED. |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL |
| | ROBERT MCDOUGAL AT 659-8096 EXT.8202. |