| Plan Review Notes For Permit 00060357 |
| Permit Number |
00060357 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************UNSAT ******************** | | | | | | 1)NOTE: PLEASE SEE E3.1. MISSING BRANCH | | | CIRCUIT # FOR OUTLETS.(PETER`S OFFICE) | | | | | | 2)NOTE: SUBMIT LOAD CALCULATION FOR | | | EACH PANEL. YOU SHOW THE SAME LOAD ON | | | EACH PANEL? PLEASE NOTE THAT CONTINUOUS | | | LOADS ARE FIGURED AT 125% (LIGHTING) | | | PLEASE GIVE A BREAKDOWN ON CALCS. | | | OUTLETS, SQ.FT ETC. | | | | | | 3)NOTE: PANEL 'H8A' SHOWS AIC RATING | | | AT 14,000? THIS DOES NOT CORRELATE WITH | | | STANDARD RATINGS OF EQUIPMENT. PLEASE | | | CHECK. | | | | | | 4)NOTE: PLEASE INDICATE ON PLANS THE | | | MAIN DISCONNECT SIZE FOR THIS SPACE. | | | IS IT THE SAME AS THE ON SHOWN FOR SMITH | | | BARNEY? | | | | | | 5)PLEASE SHOW PANEL SCHEDULES SHOWING | | | CIRCUITS AS LIGHTING CIRCUITS TO CORRE- | | | -LATE WITHROOM #S. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORAMTION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|