Plan Review Notes
Plan Review Notes For Permit 00060357
Permit Number 00060357
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************UNSAT ********************
  
 1)NOTE: PLEASE SEE E3.1. MISSING BRANCH
 CIRCUIT # FOR OUTLETS.(PETER`S OFFICE)
  
 2)NOTE: SUBMIT LOAD CALCULATION FOR
 EACH PANEL. YOU SHOW THE SAME LOAD ON
 EACH PANEL? PLEASE NOTE THAT CONTINUOUS
 LOADS ARE FIGURED AT 125% (LIGHTING)
 PLEASE GIVE A BREAKDOWN ON CALCS.
 OUTLETS, SQ.FT ETC.
  
 3)NOTE: PANEL 'H8A' SHOWS AIC RATING
 AT 14,000? THIS DOES NOT CORRELATE WITH
 STANDARD RATINGS OF EQUIPMENT. PLEASE
 CHECK.
  
 4)NOTE: PLEASE INDICATE ON PLANS THE
 MAIN DISCONNECT SIZE FOR THIS SPACE.
 IS IT THE SAME AS THE ON SHOWN FOR SMITH
 BARNEY?
  
 5)PLEASE SHOW PANEL SCHEDULES SHOWING
 CIRCUITS AS LIGHTING CIRCUITS TO CORRE-
 -LATE WITHROOM #S.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORAMTION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372