| 2001-01-08 00:00:00 | SECOND CHECKLIST: |
| | 1-IMPACT FEES WERE NOT PAID. |
| | 2-PROVIDE CURRENT PRODUCT APPROVAL FOR |
| | SLIDING GLASS DOORS. OR PROVIDE A |
| | COMPLETE SITE SPECIFIC ENGINEERING |
| | ANALYSIS WITH ALL CALCULATIONS, COPIES |
| | OF STRUCTURAL TESTS PERFORMED AS PER |
| | ASTM E-330, COMPLETE INSTALLATION |
| | DETAILS INCLUDING FASTENING TO THE |
| | STRUCTURE. AND INCLUDE SITE SPECIFIC |
| | FORM (ATTACHED) SIGNED, SEALED AND |
| | DATED BY THE MANUFACTURER ENGINEER AND |
| | THE ARCHITECT OF RECORD. |
| | 3-PRODUCT APPROVAL FOR SKYLIGHT IS |
| | INCOMPLETE. MISSING COPIES OF THE |
| | APPROVED DRAWINGS. |
| | 4-TWO HOUR CONCRETE BLOCK: PROVIDE |
| | CERTIFICATION FROM MANUFACTURER |
| | ENGINEER STATING THAT CONCRETE BLOCK |
| | EQUIVALENT THICKNESS COMPLIES WITH |
| | ASTM C140 FOR FIRE RESISTANCE. |
| | SECTION 709.3 SBC 1997. |
| | 5-PROVIDE PRODUCT APPROVAL FOR WINDOW |
| | MULLIONS. |
| | 6-COMPLETELY SPECIFY CEILING CONSTRUCT'N |
| | AT ENTRY AND REAR PORCHES. INCLUDE ALL |
| | FASTENERS TYPES AND SPACING. SECTION |
| | 2504 SBC 1997. |
| | 7-REVISE ROOF TRUSS ANCHOR SCHEDULE AS |
| | REQUIRED. NEED TO SPECIFY WOOD TO WOOD |
| | CONNECTORS AT PORCHES' ROOF TRUSSES |
| | ANCHORED TO WOOD BEAMS. |
| | 8-OWNER/AGENT TO SIGN AND DATE THE |
| | ENERGY CALCULATIONS. |
| | 9-PROVIDE A CURRENT PRODUCT APPROVAL |
| | FOR STORM PANELS. |