| Plan Review Notes For Permit 00060287 |
| Permit Number |
00060287 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED********************************** | | | 1. AUXILIARY DRAIN TO BE RUN SEPERATE | | | FROM THE CONDENSATE DRAIN. 1997 SMC | | | 304.8.6.1. | | | 2. NO COMBUSTIBLES ALLOWED IN RETURN AIR | | | PLENUM.SMC 609.1.1. | | | | | | 3. PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89. | | | 4. REQUIRES AIR BALANCE SCHEDULE PER | | | 1997 SMC 501.2. |
|