Plan Review Notes
Plan Review Notes For Permit 00060287
Permit Number 00060287
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DENIED**********************************
 1. AUXILIARY DRAIN TO BE RUN SEPERATE
 FROM THE CONDENSATE DRAIN. 1997 SMC
 304.8.6.1.
 2. NO COMBUSTIBLES ALLOWED IN RETURN AIR
 PLENUM.SMC 609.1.1.
  
 3. PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89.
 4. REQUIRES AIR BALANCE SCHEDULE PER
 1997 SMC 501.2.