| Plan Review Notes For Permit 00060287 |
| Permit Number |
00060287 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT THE AIC RATINGS | | | OF MAINS/PANELS.215-5 MAINS/PANELS MUST | | | BE RATED FOR THE AVAILABLE FAULT CURRENT | | | PER 110-9. | | | | | | 2)NOTE: PLEASE SUBMIT A CLEAR DETAILED | | | RISER DIAGRAM,.SHOW THE ATTACHMENT FOR | | | THE GROUNDING FOR TRANSFORMER. | | | ALSO NOTE THAT YOU HAVE 70AMP OC PROTECT | | | -ION GOING TO A 60 AMP DISCONNECT? | | | PLEASE CORRELATE. | | | | | | 3)NOTE: PLEASE SHOW THE LOAD CALCULATION | | | WITH THE BREAKDOWN OFCALCULATIONS. | | | PLEASE INCLUDE ALL CONTINUOUS LOADS AT | | | 125% (LIGHTING) ETC. 215-5/220 | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORAMTION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. 561-659-8096 EXT 8372 |
|