Plan Review Notes
Plan Review Notes For Permit 00060287
Permit Number 00060287
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT THE AIC RATINGS
 OF MAINS/PANELS.215-5 MAINS/PANELS MUST
 BE RATED FOR THE AVAILABLE FAULT CURRENT
 PER 110-9.
  
 2)NOTE: PLEASE SUBMIT A CLEAR DETAILED
 RISER DIAGRAM,.SHOW THE ATTACHMENT FOR
 THE GROUNDING FOR TRANSFORMER.
 ALSO NOTE THAT YOU HAVE 70AMP OC PROTECT
 -ION GOING TO A 60 AMP DISCONNECT?
 PLEASE CORRELATE.
  
 3)NOTE: PLEASE SHOW THE LOAD CALCULATION
 WITH THE BREAKDOWN OFCALCULATIONS.
 PLEASE INCLUDE ALL CONTINUOUS LOADS AT
 125% (LIGHTING) ETC. 215-5/220
  
 PLEASE SUBMIT ALL THE ABOVE INFORAMTION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL. 561-659-8096 EXT 8372