Plan Review Notes
Plan Review Notes For Permit 00060164
Permit Number 00060164
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00 
  
  
 ************DENIED*******************
  
 SBC 104.2.2
  
 1) PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO DADE PRODUCT APPROVALS FOR:
 MULLIONS USED,ONE LIGHT FROSTED
 FRENCH DOOR,OUTSWING SINGLE HUNG
 FRENCH DOOR,OUTSWING HOLLOW METAL
 DOOR,OUTSWING (FRONT DOOR) W/SIDE-
 LITE,AND FIREPLACE WITH U.L.LISTING
  
 2)PROVIDE MANUEL J, MISSING FROM
 ENERGY CALCS.
  
 3) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED,IMPACT FEES MUST BE PAID TO
 PALM BEACH CO.,THE PERMIT STAMPED BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.
  
 4)PROVIDE ENGINEERING FOR ALL BUTT
 GLASS OPENINGS.